11.90 11 Alarms
11.11 Alarm list ACKNOWLEDGE
6117
MD 0001: CPU load
Cause:
Effect:
Remedy:
PLC MD 1 greater than 20 %
PLC STOP
Correct MD
6118
MD 0003: Alarm runtime
Cause:
Effect:
Remedy:
PLC MD 3 greater than 2500 s
PLC STOP
Correct MD
6119
MD 0005: Cycle time
Cause:
Effect:
Remedy:
PLC MD 5 greater than 320 ms
PLC STOP
Correct MD
6121
MD 0006: Last MC 5 time
Cause:
Effect:
Remedy:
PLC MD 6 greater than 31
PLC STOP
Correct MD
6122
This arrangement n. permitted
Cause:
Remedy:
A wrong coupling area position ( 0) was set at the link module master
PLC by DIP-FIX (S6).
Set DIP-FIX (S6) properly