Siemens SIMATIC NET PROFIBUS Manual de servicio Pagina 32

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 238
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 31
Overview of PROFIBUS DP
DP Base Programming Interface for CP 5613/CP 5614
32
C79000-G8976-C108-01
2.11 DP-V1 As an Extension of DP
Overview of the DP Protocol with DP-V1 Extensions
Apart from cyclic DP master operation (see Section 2.3), two further extensions are
defined as DP-V1: DPC1 and DPC2. The paragraphs below contain an overview of
these extensions:
DPC1
DP
DPC2
DP slave with DP-V1
additional functions
User program User program
DP/DPC1 prog.
interface
DPC2 prog.
interface
PG/PC
DP master class 1
PG/PC
DP master class 2
Acycl. operation
MSAC_C2
Cycl.
operation
MSCY C1
Acycl.
operation
MSAC_C1
DP-V1 Master Class 1 (DPC1)
With DPC1, a cyclic DP master can also send or read slave data and receive and
acknowledge alarms. These data are not process data but slave-specific additional
data (for example, new parameters). These data are not sent cyclically and must
be acknowledged explicitly by the slave.