Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
C79000-G8976-C108-01
187
Example of Device-Related Diagnostic Data with Status Message
The following diagram shows status diagnostic data based on the scheme outlined
above.
MSB LSB
7 6543210
Device-related
diagnostics:
00
000111
Status type: status message
1
000000
1
Slot number 2 0 0 0 0 0 0
1
0
Specifier: no further
information
0 0000000
User diagnostic data: 5
average temperature
00000
1
0
1
User diagnostic data:
temperature value
(unsigned 16)
x xxxxxxx
x xxxxxxx
Example of Device-Related Diagnostic Data with Alarm Message
The following diagram shows alarm diagnostic data based on the scheme outlined
above.
Device-related
diagnostics:
00
00100 1
Alarm type: process alarm
0
00000
1
0
Slot number 3 (valve B) 0 0 0 0 0 0
11
Specifier: alarm enters state 0 0 0 0 0 0 0
1
User diagnostic data: 0x50
(upper pressure limit
exceeded)
0 101000 0
User diagnostic data (time
of day, 4 bytes)
x xxxxxx x
x xxxxxx x
x xxxxxx x
x xxxxxx x
Comentarios a estos manuales