Web-Based Management (WBM)
4-19
Industrial Ethernet OSM/ESM Network Management
C79000-G8976-C137-08
Standby Status
Passive:
The OSM/ESM is passive; in other words, it does not pass on any packets via the
standby ports.
Active:
The OSM/ESM is active; in other words, it passes on packets via the standby
ports.
RM Mode
Disabled:
The OSM/ESM is not operating as the redundancy manager (RM).
Enabled:
The OSM/ESM is operating as the redundancy manager (DIP switch set to “RM
on”).
RM Status
Passive:
The OSM/ESM is operating as the redundancy manager and has opened the ring;
in other words, the line of OSMs/ESMs attached to it (ports 7 and 8) is operating
without problems. The passive status is also indicated when the RM mode is
disabled.
Active:
The OSM/ESM is operating as the redundancy manager and has closed the ring;
in other words, the line of OSMs/ESMs attached to it (ports 7 and 8) is interrupted
(fault or error). The redundancy manager switches the link between ports 7 and 8
through and reestablishes a functioning bus configuration.
Power Line 1
Up: Power supply 1 (line 1) is applied.
Down: Power supply 1 is not applied or has a value less than
14 V.
Power Line 2
Up: Power supply 2 (line 2) is applied.
Down: Power supply 2 is not applied or has a value less than
18 V.