The Static Trip III consists of four models:
A standard feature of the Static Trip IIIC, IIICP, and IIICPX trip
units is an alarm output. Any measured parameter can be set to
activate the alarm based on threshold and time delay set points.
These units also include several logging functions for recording
trip events, pickup conditions, alarm activity, and min/max
measured values.
Static Trip IIIC, IIICP, and IIICPX trip units have added
communication ability. Metered parameters can be displayed
and configured locally on the BDU or remotely via the RS-485
communications port through the ACCESS system.
III Basic Overcurrent Protection
IIIC Added Communications and Current Metering
IIICP Added Power Metering
IIICPX Extended Protective Relaying
Static Trip Family
Measured Value STIIIC STIIICP/CPX Accuracy
Phase Current 1.00%
Average Current 1.00%
Ground Current 1.00%
Phase Line-to-Neutral Voltage 1.00%
Average Line-to-Neutral Voltage 1.00%
Line-to-Line Voltage for all Phases 1.00%
Average Line-to-Line Voltage 2.00%
kW Total for all Phases 2.00%
kWh Total for all Phases 2.00%
kW Reverse 2.00%
kW Demand 2.00%
kVA 2.00%
kVAR 2.00%
kVARh Total for all Phases 2.00%
Power Factor 4.00%
Frequency 0.25%