Siemens DTU3005-B Especificaciones Pagina 25

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 88
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 24
25
Harmonic Effects All harmonics cause additional heat in conductors and other
distribution system components. Negative sequence harmonics
can be problematic in induction motors. The reverse phase
rotation of negative harmonics reduces forward motor torque
and increases the current demand.
Zero sequence harmonics add together, creating a single-phase
signal that does not produce a rotating magnetic field. Zero
sequence harmonics can cause additional heating in the neutral
conductor of a 3Ø, 4-wire system. This can be a major problem
because the neutral conductor typically is not protected by a
fuse or circuit breaker.
Vista de pagina 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 87 88

Comentarios a estos manuales

Sin comentarios