Appendix E: Device Data Format
92 Siemens Energy & Automation, Inc.
Alarm Function Status
Note: When bit numbers are
specified, Bit 15 is the
highest order bit in the
PLC register.
46 Bit Contents
15–10 Unused
9 Harmonic Distortion Alarm
8Under PF Lag Alarm
7 Over PF Lead Alarm
6 Over kVAR Alarm
5 Over kVA Alarm
4 Over kW Demand Alarm
3Over kW Alarm
2 Over Amp Demand Alarm
1 Grnd Over Amp Alarm
0 Over Amp Alarm
Protective Relay Status 47 Bit Contents
15–8 Unused
7 Under Frequency Alarm
6 Over Frequency Alarm
5Over Reverse kW Alarm
4 Overvoltage Alarm
3 Voltage Unbalanced Alarm
2 Undervoltage Alarm
1 Current Unbalanced Alarm
0 Neutral Over Amp Alarm
Event Counter 48 0...65535
System Error Flag 49 0 = No System Errors
1 = EEPROM Write Error
2 = Status Update Error
3 = Clear Trip Log Error
4 = Trip Log Entry Error
5 = Breaker Test Error
6 = Trip Error
THD Phase A 50 0-100
THD Phase B 51 0-100
THD Phase C 52 0-100
THD Neutral 53 0-100
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
Device Command Data Retrieved From PLC (Energy/Comm)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Reset All Demand Values Unused for Command 1
2 = Reset All Hour Counters Unused for Command 2
3 = Close Breaker Unused for Command 3
4 = Open Breaker Unused for Command 4
Real-Time Device Data Stored in PLC (Energy/Comm) (Continued)
Real-Time Data Register Location in
PLC Block
1
Range or Contents