Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 129
General Trip of Device 38 ms since fault (-1 = no occurance)
Trip by thermal overload
protection 1
39 ms since fault (-1 = no occurance)
Trip by thermal overload
protection 2
40 ms since fault (-1 = no occurance)
Back-up Overcurrent: General Trip 41 ms since fault (-1 = no occurance)
External Trip 1: General Trip 42 ms since fault (-1 = no occurance)
External Trip 2: General Trip 43 ms since fault (-1 = no occurance)
Diff. Prot.: Blocked by
harmonics L1
44 ms since fault (-1 = no occurance)
Diff. Prot.: Blocked by
harmonics L2
45 ms since fault (-1 = no occurance)
Diff. Prot.: Blocked by
harmonics L3
46 ms since fault (-1 = no occurance)
Differential Protection: General Trip 47 ms since fault (-1 = no occurance)
Differential Protection: L1 48 ms since fault (-1 = no occurance)
Differential Protection: L2 49 ms since fault (-1 = no occurance)
Differential Protection: L3 50 ms since fault (-1 = no occurance)
Differential Protection: Trip by Idiff> 51 ms since fault (-1 = no occurance)
Differential Protection: Trip by
Idiff>>
52 ms since fault (-1 = no occurance)
Reserved 53–56 For Future Expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
2. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter and the valid bit indi-
cates that the device has sucessfully updated the value in the status bit (true = 1, false = 0).
Device Command Data Retrieved From PLC (7UT512)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
2 = Reset LEDs Unused
3 = Activate Parameter Set A Unused
4 = Activate Parameter Set B Unused
5 = Activate Parameter Set C Unused
6 = Activate Parameter Set D Unused
10 = General Command 2nd Word: [Typ] in high byte, [Inf] in low byte
Real-Time Device Data Stored in PLC (7UT512) (Continued)
Function Register Location in
PLC Block
1
Range or Contents