Appendix E: Device Data Format
120 Siemens Energy & Automation, Inc.
General Status Word 6:
2
21 Bit Contents
15 DC-Q10 pos (Valid)
14 DC-Q10 pos (Status)
13 DC-Q8 pos (Valid)
12 DC-Q8 pos (Status)
11 DC-Q6 pos (Valid)
10 DC-Q6 pos (Status)
9DC-Q5 pos (Valid)
8DC-Q5 pos (Status)
7 DC-Q01 pos (Valid)
6DC-Q01 pos (Status)
5DC-Q1 pos (Valid)
4DC-Q1 pos (Status)
3CB-Q0 pos (Valid)
2CB-Q0 pos (Status)
1 Error DC pos Q2 (Valid)
0 Error DC pos Q2 (Status)
General Status Word 7:
2
22 Bit Contents
15 Starting Time Supervision Active (Valid)
14 Starting Time Supervision Active (Status)
13 59-Overvoltage protection is ACTIVE (Valid)
12 59-Overvoltage protection is ACTIVE (Status)
11 27-Undervoltage protection is ACTIVE (Valid)
10 27-Undervoltage protection is ACTIVE (Status)
9 46-Negative seq. is ACTIVE (Valid)
8 46-Negative seq. is ACTIVE (Status)
7 Motor start protection is ACTIVE (Valid)
6 Motor start protection is ACTIVE (Status)
5DC-Q2 pos (Valid)
4DC-Q2 pos (Status)
3DC-Q16 pos (Valid)
2DC-Q16 pos (Status)
1DC-Q15 pos (Valid)
0DC-Q15 pos (Status)
General Status Word 8:
2
23 Bit Contents
2–15 Not Used
1 Trip Circuit Interrupted (Valid)
0 Trip Circuit Interrupted (Status)
Number of Last Fault 24 0…32767, 0 = no faults
Fault Date/Time (ms) 25 0…59999 (ms )
Fault Date/Time (h/m) 26 High byte: HH (0…23), Low byte: MM (0…59)
Fault Date/Time (m/d) 27 High byte: MM (1…12); Low byte: DD (1…31)
Fault Date/Time (y) 28 Year: YY (00…99)
Interrupted current:
Phase L1 (I/I
n
)
29 ms since fault (-1 = no occurance)
Interrupted current:
Phase L1 (I/I
n
)
30 Low word
Interrupted current:
Phase L1 (I/I
n
)
31 High word
Interrupted current:
Phase L2 (I/I
n
)
32 ms since fault (-1 = no occurance)
Interrupted current:
Phase L2 (I/I
n
)
33 Low word
Interrupted current:
Phase L2 (I/I
n
)
34 High word
Interrupted current:
Phase L3 (I/I
n
)
35 ms since fault (-1 = no occurance)
Real-Time Device Data Stored in PLC (7SJ531) (Continued)
Function Register Location in
PLC Block
1
Range or Contents
Vista de pagina 123