Siemens S7-400PLC Especificaciones Pagina 74

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 486
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 73
Power supply modules
3.9 Power supply modules PS 407 10A (6ES7407-0KA02-0AA0) and PS 10A R (6ES7407-0KR02-0AA0)
S7-400 Automation System Module Data
74 Reference Manual, Edition 09/2009, A5E00850736-06
3.9 Power supply modules PS 407 10A (6ES7407-0KA02-0AA0) and
PS 10A R (6ES7407-0KR02-0AA0)
Function
The power supply modules PS 407 10A (standard) and PS 407 10A R (redundancy-capable,
see section Redundant power supply modules (Page 51)) are designed for connection to an
AC line voltage of 85 to 264 V or DC line voltage of 88 to 300 V and supply 5 VDC / 10 A
and 24 VDC /1 A on the secondary side.
Operator Controls and Indicators on the PS 407 10A and the PS 407 10A R
36$
.$$$
;

)05
%$77,1',&
%$77
%$77
2))
,17)
%$)
%$77)
'&9
'&9
%$77)
%$77 %$77
/('V,17)%$)
%$77)%$77)9
'&9'&
0RXQWLQJVFUHZ
0RXQWLQJVFUHZ
)05EXWWRQ)DLOXUH0HVVDJH5HVHW
8QGHUFRYHU
8QGHUFRYHU
%DWWHU\FRPSDUWPHQW
6ZLWFK%$77,1',&
%$772))%$77
SLQSRZHUFRQQHFWRU
6WDQGE\VZLWFKGRHVQRWFXWRIIPDLQV
Figure 3-5 Operator controls and indicators of the PS 407 10A and PS 407 10A R
Power connection
An AC connector is used for connecting the PS 407 10A and the PS 407 10A R to both an
AC and a DC supply.
Polarity reversal of L+ and L-
Reverse polarity of L+ and L- with supply voltages of between 88 and 300 VDC has no effect
on the function of the power supply. The connection should be made as described in the
instructions in the Installation Manual.