Digital modules
4.8 Digital input module SM 421; DI 16 x DC 24 V (6ES7421-7BH01-0AB0)
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
119
Behavior when the input delay equals 0.1 ms or 0.05 ms and an error occurs
If you have set the following parameters:
● Input delay: 0.1 ms or 0.05 ms
● Reaction to error: "Keep Last Value" (KLV) or "Substitute Value" (SV)
● Set substitution value "1"
In the event of a fault on a channel that has a 1 signal, the following could occur:
● A 0 signal may be briefly output
● If configured, a hardware interrupt may be generated.
This occurs before the last valid value or substitute value "1" is output.