RS 485 repeater
10.4 RS 485 repeater in ungrounded and grounded operation
S7-400 Automation System Module Data
406 Reference Manual, Edition 09/2009, A5E00850736-06
10.4 RS 485 repeater in ungrounded and grounded operation
Grounded or ungrounded
The following applies to the RS 485 repeater:
It is grounded, if all other nodes on the segment are also operated on ground potential
It is ungrounded, if all other nodes in the segment are operated with an ungrounded
potential
Note
Bus segment 1 is grounded if you connect a programming device with a pure MPI
interface to the PG/OP socket of the RS 485 repeater. The segment is grounded,
because the MPI in the PG is grounded, and the PG/OP socket of the RS 485 repeater is
connected internally with bus segment 1. This does not apply when the programming
device has a combination MPI/DP interface.
Grounded operation of the RS 485 repeater
For grounded operation of the RS 485 repeater, you must jump terminals "M" and "PE" on
the top of the RS 485 repeater.
Ungrounded operation of the RS 485 repeater
For ungrounded operation of the RS 485 repeater, "M" and "PE" on the top of the RS 485
repeater must not be interconnected. In addition, the supply voltage to the RS 485 repeater
must be ungrounded.