Siemens S7-400PLC Especificaciones Pagina 338

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 486
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 337
Analog modules
5.26 Analog output module SM 432; AO 8 x 13 Bit (6ES7432-1HF00-0AB0)
S7-400 Automation System Module Data
338 Reference Manual, Edition 09/2009, A5E00850736-06
Formation of analog values
Resolution (including overshoot range) 13 bits
Conversion time (per channel)
In the ranges 1 to 5 V and 4 to 20 mA
420 µs
In all ranges
300 µs
Basic execution time of the module (all channels enabled)
In the ranges 1 to 5 V and 4 to 20 mA
3.36 ms
In all the other ranges
2.4 ms
Settling time
With resistive load
0.1 ms
With capacitive load
3.5 ms
With inductive load
0.5 ms
Noise suppression, error limits
Noise suppression at f = n (f1 ± 1 %), (f1 = interference frequency) n= 1.2...
Common-mode interference (UCM < AC 3 Vpp/50
Hz)
> 60 dB
Crosstalk between outputs > 40 dB
Operational limit (across temperature range, relative to input range)
Voltage output
± 10 V
0 to 10 V
1 to 5 V
± 0,5 %
± 0,5 %
± 0,5 %
Current output
± 20 mA
4 to 20 mV
± 1 %
± 1 %
Basic error limit (operational error limit at 25° C, relative to output range)
Voltage output
± 10 V
0 to 10 V
1 to 5 V
± 0,5 %
± 0,5 %
± 0,5 %
Current output
± 20 mA
0 to 20 mA
± 0,5 %
± 0,5 %
Temperature error (relative to output range) ± 0.02 % K
Linearity error (relative to output range) ± 0,05 %
Repetition accuracy (in transient state at 25° C,
relative to input range)
± 0,05 %
Output ripple; range 0 Hz to 50 kHz (relative to output
range)
± 0,05 %
Status, interrupts, diagnostics
Interrupts None
Diagnostic functions None
Injection of substitution values No
Vista de pagina 337
1 2 ... 333 334 335 336 337 338 339 340 341 342 343 ... 485 486

Comentarios a estos manuales

Sin comentarios