Modbus Commands
C-19
TIWAY I Gateway User Manual
The
diagnostics codes supported are described in the following paragraphs.
Diagnostic
Code — 00
I000000
0000 | any
data
Diagnostic code
Information frame
When
Function Code 08 uses diagnostic code 0000, any data passed in the
information field is returned to the host computer by the Gateway
. The
Gateway will send Primitive 02 to the secondary
. If the secondary has a
fatal error
, communications loopback is not performed to indicate fatal error
.
The purpose of this command is to determine if the communications are
functioning correctly
, and may be used in conjunction with diagnostic tests
described later
.
Diagnostic
Code — 01
I000000
0001 | 00
00
0001 |
FF 00
Diagnostic code
Information frame
or
When
Function Code 08 uses diagnostic code 0001, the information frame
can contain 0000 or FF00. This function causes the Gateway to clear all
internal counters and registers. If the information frame contains FF00, the
Communications Event Log will be cleared. If any other value is passed in
the information field, the Communications Event Log will not be cleared,
and no response will be returned.