Gateway Installation and Configuration
3-10
TIWAY I Gateway User Manual
3.3 Switches and Indicator Lights
I000000
Reset
Self-Test
Online/Offline
Online
Offline
Figure 3-5 Gateway
Operation Switches
The Online/Offline switch, when placed in the Online position, allows the
Gateway to communicate with the network and the other systems connected
to the Gateway
. In the Offline position, the Gateway is disconnected from
the network. This prevents access to the network while secondaries are
being changed or while maintenance is being performed. The position of this
switch is read before each communication cycle, so a reset of the Gateway is
not necessary each time the Online/Offline switch position is changed.
The Self-T
est button initiates a set of Gateway diagnostic tests, including a
standalone Gateway communications loopback test. This test requires a
special hardware set-up, using the loopback connector supplied with the
Gateway
. This procedure is described more fully in the section on Diagnostic
T
ests. The Gateway must have the Online/Offline switch in the Offline
position to initiate the diagnostic tests.
Pressing the Reset button causes a hardware reset of the Gateway and
initiates the power
-on diagnostic test. The power-on test is explained in
more detail in the section on Diagnostic T
ests.
Online/Offline
Switch
Self-T
est Button
Reset Button