Network Installation
2-7
TIWAY I Gateway User Manual
The
terminating resistors must be used to ensure that the main line cable is
properly terminated and biased for improved reliability
. Each tap housing is
supplied with terminating resistors to connect to the ends of the main line
cable. At each end, a terminating resistor must be connected between LLM+
and the cable shield and also between LLM– and the cable shield inside the
tap housing.
I000000
G
W
B
G
W
B
GWB
Termination
Resistors:
68
ohms
5%
1/4 watt
Cable
to Module
Network Cable
Input Output
Figure 2-4 Terminating
the Local Line
Siemens Industrial Automation recommends Belden 9860 twisted-pair
cabling or its equivalent for use as the Local Line network spine. Belden
9271 or its equivalent should be used for the dropline. Brands other than
those listed here will be specified by Siemens upon request.
Some major points to consider during the planning phase of a Local Line
network are the following.
From the start, allow for system growth. Make provisions for the
attachment of additional computing devices by routing cables through
all probable areas of future plant expansion.
Always make the network flexible enough to allow for re-arrangement
of plant equipment.
Since network system noise is usually picked up by its interconnecting
wiring, take steps during installation to bypass or eliminate noise
sources.
If cable redundancy is required, make sure the two cables are never
routed along the same path, since the environmental and other factors
which disable one cable will very likely disable the second cable.
Ter
minating the
Main Line Cable
Twisted-Pair
Cabling
Important Planning
Considerations