Siemens v1.0 Manual de servicio Pagina 136

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 202
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 135
Example "PID control"
4.1 Introduction
STEP 7 Basic V10.5
136 Getting Started, 12/2009, A5E02651459-01
The setpoint "
w
" has been predefined. The setpoint in the following example is a
temperature setting of 75°C in the heating chamber. The error (
e
) is calculated from the
setpoint (
w
) and the actual value (
y
). The error will be converted by the controller (K) into a
controlled variable (
u
). The controlled variable changes the actual value (
y
) via the controlled
system (G). The controlled system (G) in this example is the temperature control in the
heating chamber, for example, by increasing or decreasing the energy supply.
In addition to the controlled system (G), the actual value (
y
) can be altered through
disturbance variables (
d
). A disturbance variable in this example may be an unwanted
temperature change in the heating chamber, for example, caused by a change in the outside
temperature.
Use of the PID controller
In the example project you use the PID controller to reach the desired temperature of 75°C
as quickly as possible and to maintain the setpoint as constant as possible.
In this example, the setpoint can be exceeded because the heating element continues to
emit heat even after it has been switched off. This effect is known as "overshoot"; it occurs
when there is a time delay between the control and the measurement of the actual value.
The following figure shows the possible characteristic of the temperature curve after the
initial switching on of the machine:
r&
W
7HPSHUDWXUHLQWKH
KHDWLQJFKDPEHU
DFWXDOYDOXH
5HTXLUHGWHPSHUD
WXUHVHWSRLQW




Vista de pagina 135
1 2 ... 131 132 133 134 135 136 137 138 139 140 141 ... 201 202

Comentarios a estos manuales

Sin comentarios