Siemens SIMATIC NET Especificaciones Pagina 242

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 268
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 241
232 Siemens Simatic S7 Driver Online Help
To make sure you receive driver messages in Alarm History
[1] Shut down FIX/iFIX and the I/O Driver Power Tool.
[2] Start the System Configuration Utility (SCU) and select Tasks from the
Configure menu. The Task Configuration dialog box appears.
[3] Enter the Base path and IOCNTRL.EXE in the Filename field.
[4] Enter the /a command line parameter in the Command Line field.
[5] Select the Background option button and click Add.
[6] Save the SCU configuration and start FIX/iFIX. The SI7 Server automatically
starts and you should see a message that the driver started.
See Also
Tools for Troubleshooting the SI7 I/O Driver
Automatic driver startup does not work
To automatically start the driver, install it in your root FIX or iFIX directory. If you
have not installed the driver in this directory, uninstall it and then re-install it in the
proper path.
To start the Power Tool and verify that it is configured correctly
[1] Verify that the channels, devices, and datablocks are enabled.
[2] Make sure the Auto Start option is turned on:
[a] Select Setup from the Options menu. The Setup dialog box appears.
[b] Select the Advanced tab.
[c] Click the Auto Start On option from the I/O Server area.
Vista de pagina 241
1 2 ... 237 238 239 240 241 242 243 244 245 246 247 ... 267 268

Comentarios a estos manuales