8 APPENDIX
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL | APPENDIX D
TO NEXT
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTES 2 AND 8
RELAY CONTACTS
SEE NOTE 6
NOTE:
WITH HTRI-S, TERMINALS
5 AND 6 ARE NOT USED.
SUPERVISED SWITCH
SEE NOTES 1, 5, 8 AND 9
FROM CONTROL PANEL
OR FROM PREVIOUS
ADDRESSABLE DEVICE
1
HTRI-S/-R
2
3
4
5
8
7
6
LINE 1
LINE 1
LINE 2
LINE 2
SEE NOTE 7
NOTES:
1. All supervised switches
must be held closed and/or
open for at least a quarter of
a second to guarantee
detection.
2. Use ULI listed EOL Model
EL-33 with 3.6K, ¼W
resistor, P/N 140-820185.
Order Model EL-33
separately.
3. HTRI is polarity insensitive.
Line 1 and Line 2 can be
either line of the loop.
4. Electrical ratings:
Voltage maximum: 30 VDC
Current maximum:
1mA during polling
5. Supervised switch ratings:
Voltage maximum: 27 VDC
Current maximum: 3.5mA
during polling
Contact resistance maximum:
10 ohms
Maximum cable length:
200 feet (18 AWG)
C
Line to line
: 0.02uF
C
Line to shield
: 0.04uF
Max line size: 14 AWG
Min line size: 18 AWG
6. Relay contact ratings:
4A, 125 VAC resistive
4A, 30 VDC resistive
Inductive:
3.5A, 120 VAC (0.6P.F.)
3.0A, 30 VDC (0.6 P.F.)
2.0A, 120 VAC (0.4 P.F.)
2.0A, 120 VAC (0.35 P.F.)
2.0A, 30 VDC (0.35 P.F.)
The relay is shown in
standby condition.
7. Terminal 5 must be
connected to earth ground.
a. Use wire nuts to pass the
shield wire through the
electrical box with NO
connection to the device
terminal block or to local
ground.
b. Use shielded wire to
connect the switch wiring.
c. Tie the switch wiring shield
to the DLC wiring shield. Do
not connect shield to
terminal 5 or the local earth
ground.
8. For proprietary burglary
application:
a. Use an HTSW-1 tamper
switch to monitor the main
enclosure.
b. Monitor each HTRI-S/-R/-D
related to this application
continuously by using a
listed motion detector (to
prevent tampering).
9. In supervisory:
HTRI-S/-R draws 1mA
HTRI-D draws 1mA
Terminal 5 of the HTRI-S/-D/-R must be connected to a known good earth ground for
proper operation.
HTRI-D
NOT USED
TO NEXT
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTES 2 AND 8
END OF LINE DEVICE
SEE NOTES 2 AND 8
SUPERVISED SWITCH
SEE NOTES 1, 5, 8 AND 9
SUPERVISED SWITCH
SEE NOTES 1, 5, 8 AND 9
FROM CONTROL PANEL
OR FROM PREVIOUS
ADDRESSABLE DEVICE
1
2
3
4
5
8
7
6
LINE 1
LINE 1
LINE 2
LINE 2
SEE NOTE 7
Vista de pagina 59