4-22 VOICE SYSTEM
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL | CHAPTER 4
Phone Page Phone Page allows the user to send the emergency page message from the
firefighters party line to all speaker groups in the system. Keying the microphone on
the Emergency Page microphone will shut off the Phone Page.
To perform a Phone Page, follow the steps listed below.
1. Depress the All Page switch (or depress Select Page and selected Speaker
Group switches).
2. The All Page and all Speaker Group switch LEDs flash green.
3. Depress the Phone Page switch.
4. The Phone Page, All Page and Speaker Group switch LEDs turn on steady
green.
5. The operator now can speak and make the page to the speaker groups.
6. To end Phone Page, depress the Phone Page and the All Page switch again.
7. The Phone Page, All Page and Speaker Group switch LEDs turn off.
Wardens Page Wardens Page allows a remote firefighter located anywhere in the building to make a
live voice page. Keying the microphone on the Emergency Page microphone will shut
off the Wardens Page.
To perform a Wardens Page, follow the steps listed below.
1. A remote firefighter lifts a Wardens Telephone Station telephone off-hook or
plugs in a Portable Firefighters Telephone.
2. The Firefighters Master Telephone (FMT) handset starts to beep indicating a
call-in.
3. The LED next to the Phone Group switch flashes green.
4. The remote firefighter calling in hears a dial tone.
5. The operator picks up the firefighters master telephone handset.
6. The operator depresses the Phone Group switch that is calling in.
7. The operator and the remote firefighter can now talk to each other.
8. The remote firefighter requests that the operator patch the phone group he
is calling in from onto the speaker group serving the area of the building the
firefighter is calling from.
9. The operator depresses the Select Page switch and the Speaker Group
switch.
10. The operator depresses the Wardens Page switch—the LED turns on
steady green.
11. The remote firefighter can now make his live voice page to the speaker
group.
12. The operator can monitor the page from the local internal speaker.
13. The operator can interrupt, override or stop the Wardens Page.
14. To end the Wardens page, de-select all depressed switches.
15. The Wardens Page and the Speaker Group switch LEDs turn off.
16. The firefighter that called in can hang up or unplug his remote telephone.
17. The Phone Group switch LED turns off.