3-4 OPERATION
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL | CHAPTER 3
In addition, the System responds to alarms with other output functions (as pro-
grammed in the Zeus tool) such as other audible signals.
An Acknowledge Alarms soft key displays in the bottom left corner of the screen.
Press this key to acknowledge each alarm and to silence the local audible. The
blinking exclamation point (!) then changes to a check mark ()). See Figure 3-4. (If the
system is programmed as NFPA 72D in the Zeus tool, it is necessary to individually
acknowledge each alarm.)
Highlight an event and press the
More Info/+ button to go to the
Devices screen, as shown in Figure
3-5. If the selected item is part of a
group, the device list will show the
primitive (individual) devices cur-
rently off-normal in the event queue.
All events in a group of the same
type (i.e., Alarm, Trouble) display
together in the devices screen.
Primitive devices that are not part of
a group display by themselves.
Depending on how the system is
programmed in Zeus, the top event
can be a device or a group.
WHERE:
First Floor Reception Area is the Group Message
! is an active event; ) is an acknowledged event
HFP-11 @ address 3:15 is the device custom message
HFP11 is the event device
10:56 is the event time
3:15 is the event device address
Smoke is the component category
Photoelectric sensor is the event device component
Pressing the Details soft key takes
you to the Details screen as shown
in Figure 3-6. The Details screen
contains information that has been
entered using the Zeus program-
ming tool, such as additional
information about the alarm location,
the number of devices in alarm (this
number can be more than one
when the device is part of a
group), the alarm types, the name
and phone number of a contact
person, icons showing the fire
equipment in the area and icons
showing special conditions.
Press the Map soft key to display a map showing the location of the event, provided
the information has been programmed using the Zeus tool. Refer to Figure 3-7. Maps
can be programmed to provide icons showing the event type. These icons are the
Figure 3-5
Alarm Devices Screen
Contact: John Sample
Phone #: 973.555.1234
AREA FIRE EQUIP:
AREA CONTAINS:
DETAILS
MAP DEVICES
BACK
ALARM LOCATION:
1st Floor Reception Area
- Lobby entrance
# Devices in ALARM: 3
ALARM TYPES:
Smoke, Heat, Flow
First Floor Reception Area
Figure 3-6
Alarm Details Screen
DETAILS
MAP DEVICES
BACK
HFP-11@address 3:15
:3-15HFP11 10:56
First Floor Reception Area
Smoke
Photoelectric sensor
HFP-11@address 3:16
:3-16HFP11 10:57 Smoke
Photoelectric sensor
HFP-11@address 3:17
:3-17HFP11 10:58 Smoke
Photoelectric sensor
!
!