Implementation steps
Chapter 5.
4. B. For an eWON with MPI port, the configuration fields are slightly different. You have to
select the protocol PPI MULTIMASTER. As the MPI port configuration is shared by the S7-200
and the S73&400 IO Servers, this combo box shows also the MPI & Profibus protocols BUT they
won't work with an S7-200. PPI MultiMaster and MPI/Profibus are mutually exclusive. It is not
possible to use the S7-200 and the S73&400 IO Servers on the MPI port at the same time.
5. To be able to poll data registers out of your PLC, you need to define and enable at least one
Topic in the lower part of the IO Server configuration page. Topics are meant to allocate common
properties to a group of tags (properties include Enable/Disable, Global Device Address, and
Poll Rate).
The snapshot below shows 2 topics enabled/configured.
Note: You might conclude the eWON cannot connect to more than 3 PLCs from the
fact there are 3 topics (A, B and C). If you need to poll tags on more than 3 PLCs,
refer to the Knowledge Base page of our Wiki here:
http://wiki.ewon.biz/Support/06_Knowledge_Base/
type How to reach more than 3 PLCs in the search field.
6. In Poll Rate, you can define the refresh rate in ms (milliseconds) applicable to all data
registers that will be included in this topic. If you leave this field blank, the default value applied
will be 2000 ms (2 seconds). The polling rate specified here applies to all tags associated with this
topic. If you have tags that need to be refreshed at a different rate, enable and configure multiple
topics.
Polling Data Registers from Siemens S7-200 PLC Series (How to) Page 8/21