5.3 Step 3 - Creating tags in the eWON
1. Go back to the configuration menu and select Tag Setup. If you are starting from scratch, the
list of tags should be empty.
2. Select Create New Tag to open the tag configuration window and enter the parameters of the
tag you want to create.
Enter a Tag Name – free text, no spaces, no symbols (-, =, %, $, @, # etc.)
Enter a Description – free text (optional)
Select S7200 as IO server
In the Address field, enter the PLC register to be polled in the PLC.
Note: The register configured in the eWON must exist in the PLC. If you enter a
wrong address (syntax problem) the tag will be rejected (an error message will
be displayed). For error messages see next point.
Examples:
Address Pointing to
MW4 the Word at address 4 (in bytes) in the Internal Memory
HCL1 the High Speed Counter number 1, read it as Signed Word
AQW5 the Word at address 5 (in bytes) in the Analog Inputs zone
IB3 the Byte at address 3 (in bytes) in the Discrete Output zone
I5#2 the bit 2 from the Byte (read ’Bit access modifer’ note below) at address 5
in the Discrete Inputs zone