Installation
4.3 Electrical installation
50
Connection inverter – DC link
In a master/slave combination, connect the DC link to the supplied cables (240 mm², single-core). Each
connection is made using two parallel cables for each polarity, thus forming a ring.
Ensure the correct polarity.
Ensure that the screws are tight and the cable has sufficient strain relief.
Location of the DC link
Figure 4-5 Position Cable connection inverter – DC link
CAUTION
The polarity in the master and slave devices differs as follows:
Copper rails for DC link in SINVERT 350/420
master and
SINVERT 500 TL master and slave
Copper rail for DC link in
SINVERT 350/420 slave
Figure 4-6 Cable connection inverter – DC link
NEG
POS
POS
NEG