Installation
4.3 Electrical installation
45
4.3 Electrical installation
Installation of cables
Cables that can cause disruptions or are themselves vulnerable to disruption, must be moved as far apart
from each other as possible.
The resistance to errors is improved by installing the cables close to the ground potential. Therefore, you
should move these cables to corners and the ground surface.
Unused wires should be grounded at least at one end.
Low-voltage cables are divided into at least four classes. Each cable class is laid in a different way, and
these cables are bundled only with (or close to) cables of their own class. Cables of different classes
must intersect at right angles, especially when they carry sensitive, interference-prone signals.
Class 1:
unshielded cables for 60 V DC
unshielded cables for 25 V AC
shielded cables for analog signals
shielded bus and data cables
Class 2:
unshielded cables for > 60 V DC and 230 V DC
unshielded cables for > 25 V AC and 230 V AC
Class 3:
unshielded cables for > 230 V AC/DC and 1000 V AC/DC
Class 4:
unshielded cables for AC/DC > 1000 V
CAUTION
Danger of mechanical damage
The cable must be laid so that it is short-circuit-proof
The cables must be bundled (three phases in a bundle) and because of the electrodynamic forces caused by short circuit
currents, they must be secured.
It is recommended that laid cables are attached every 30 cm.
WARNING
To ensure the safe operation of the devices, they may be installed and commissioned only by qualified personnel in full
compliance with the warnings referred to in this manual.
In particular, the general and regional installation and safety regulations regarding work on dangerous voltage installations
(e.g. EN 61800-5-1) and the relevant provisions regarding the use of proper tools and personal protective measures must
be observed.