AS-Interface
Introduction
AS-Interface specification
Specification V3.0
4
Overview
Scope of the AS-Interface specification
Basic data
AS-Interface Specification 3.0 describes a fieldbus system with
an AS-i master and up to 62 AS-i slaves.
The standard slaves continue to occupy one AS-i address
(1...31).
Slaves with extended addressing divide an address into an
A address (1A...31A) and a B address (1B...31B). Up to 62
A/B slaves can be connected accordingly to one AS-Interface
network.
Mixed operation of standard slaves and A/B slaves is possible
without difficulty. The AS-i master identifies automatically
which type of slave is connected. No special adjustments are
required of the user.
A digital AS-i slave has up to 4 digital inputs and 4 digital
outputs.
Transmission of digital input/output data requires a cycle time
of max. 5 ms with 31 slaves, see "Communication cycle" for
further values.
Integrated analog value transmission permits access to both
analog values and digital values without the need for any
special function blocks.
Communication cycle
Each address is queried in max. 5 ms cycle time. If two A/B
slaves are operated on one basic address (e.g. 12A and 12B), a
maximum 10 ms will be required for updating the data of both
slaves.
All slave types can be mixed and used on a single AS-Interface
network.
For more information, for example, to find out whether an
AS-Interface slave is a standard or A/B slave, refer to "Selection
and ordering data" of the relevant slave.
Available masters with the latest AS-Interface specification V3.0
CP 343-2, CP 343-2P (S7-300 / ET 200M)
DP/AS-i LINK Advanced
DP/AS-i F-Link
DP/AS-Interface Link 20E
IE/AS-i LINKPNIO
CM 1243-2 (S7-1200)
CM AS-i Master ST (ET 200SP)
More information
AS-Interface system manual
The AS-Interface system manual is available as a free download.
German
http://support.automation.siemens.com/WW/view/de/26250840
•English
http://support.automation.siemens.com/WW/view/en/26250840
Maximum number of slaves Number of
digital inputs
Number of
digital outputs
Digital Analog ASIsafe DI DO
62 62 31 62 8 = 496 62 8 = 496
Maximum cycle time (digital signals)
5 ms with 31 slaves
10 ms with 62 slaves
Up to 20 ms for A/B slaves with 4DI/4DO
Up to 40 ms for A/B slaves with 8DI/8DO