Siemens ET 73X Series Especificaciones Pagina 146

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 156
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 145
4/146
Siemens IK PI · 2015
AS-Interface
System Components and Accessories
Extension plug
4
Overview
AS-Interface extension plug:
Picture left: extension plug compact, picture right: extension plug plus
With the extension plug, it is possible to double the cable length
possible in an AS-Interface segment from 100 to 200 m.
Only one power supply unit is needed to supply power to the
slaves on the up to 200 m long segment.
The following versions of the extension plug are available:
Extension plug Compact: a passive component that can be
connected directly to the AS-Interface shaped cable
Extension plug plus: The Extension plug plus has an inte-
grated A/B slave that enables any undervoltage supply to be
signaled to the AS-Interface master. It has an M12 plug and
can be connected to the AS-Interface M12 feeder with degree
of protection IP67.
Design of an AS-Interface segment with an extension plug
With an AS-Interface segment with a cable length of more than
100 m and up to a maximum of 200 m, the extension plug is
installed in a radius of approx. ± 10 m at that point of the network
which is furthest from the power supply unit. The extension plug
is not allowed to be used in AS-Interface networks smaller than
100 m. As with all AS-Interface networks, any network structure
(line, tree, star) is possible when using the extension plug.
Only one extension plug is required per 200 m segment, even
with a tree or star structure.
Note:
With the compact extension plug and the M12 feeder
3RK1901-1NR10 (4 A), the AS-Interface shaped cable has to
be terminated using the cable terminating piece, see
"miscellaneous accessories", page 4/152.
The AS-Interface extension plug is not suitable for AS-i
Power24V networks.
Maximum network size with repeaters and extension plug (master at center of network)
Selection and ordering data
Version Article No.
3RK1901-1MX02
AS-Interface extension plug compact
Doubling of the cable length to 200 m per AS-Interface segment
With direct connection to AS-Interface shaped cable
3RK1901-1MX02
3RK1901-1MX01
AS-Interface extension plug plus
Doubling of the cable length to 200 m per AS-Interface segment
Mounting on AS-Interface M12 feeders (to be ordered separately)
• Undervoltage monitoring signal through integrated AS-Interface slave to AS-Interface master
3RK1901-1MX01
Accessories
3RX9801-0AA00
AS-Interface M12 feeders
• Transition of shaped AS-Interface cable to a standard round cable
• Current carrying capacity up to 2 A
Degree of protection IP67
3RX9801-0AA00
3RK1901-1NR10
AS-Interface M12 feeders
Transition of AS-Interface cable without U
aux
, with M12 socket
Max. 4 A
Degree of protection IP67/IP68/IP69K
3RK1901-1NR10
200 m
600 m
200 m 200 m
Repeater
Master
Slave
Power
Supply
Slave Slave Slave Slave Slave
Power
Supply
Power
Supply
Extension
Plug
Repeater
Extension
Plug
Extension
Plug
NSA0_00371c
IKPI_04_en.book Seite 146 Montag, 6. Oktober 2014 11:32 11
© Siemens AG 2014
Vista de pagina 145
1 2 ... 141 142 143 144 145 146 147 148 149 150 151 ... 155 156

Comentarios a estos manuales

Sin comentarios