4/148
Siemens IK PI · 2015
AS-Interface
System Components and Accessories
Addressing units
■
Technical specifications
■
Selection and ordering data
1)
Can be ordered only via GMC-I Messtechnik GmbH,
see Catalog IC 10, Chapter 16 "Appendix "External Partners"
2)
Not included in scope of supply of the 3RK1904-2AB02 addressing unit.
3)
For connecting the addressing unit to an AS-i network via AS-Interface
M12 feeder, a connecting cable (M12 plug to M12 connector) must be
produced and requires the following wiring:
- M12 cable plug: Pin 1 / core brown M12 plug: Pin 1
- M12 cable plug: Pin 3 / core blue M12 plug: Pin 3
- Pin 2, 4, 5 not connected.
3RK1904-2AB02 AS-Interface addressing unit
Parameters
Measuring range
•Voltage
• Current (for slaves)
V
A
2 ... 35
0 ... 0.150
Measuring accuracy in % of the measured value
•Voltage
• Current (for slaves)
%
%
± 3.5 + 2 digits
± 5 + 2 digits
Input resistance for voltage measurement k
300
Power supply
Standard power supply 4 batteries 1.5 V type AA, IEC LR6 (NEDA15) or corresponding batteries (preferably NiMH)
Recommendation for current-intensive application
4 high-grade alkaline manganese batteries 1.5 V type AA
Automatic disconnection for a longer battery life
Approx. 5 minutes (or approx. 1 minute when data exchange is active) after last operation
Ambient conditions
Ambient temperature °C 0 ... +50
Storage temperature °C
-20 ... +75 without batteries
Relative air humidity, max. %
75, condensation not permitted
Altitude above sea level, max. m
2000
Location
Only indoors
Mechanical design
Degree of protection IP40
Dimensions, W x H x D mm
84 x 195 x 35
Connection
M12 socket: Pin 1: ASI+; Pin 3: ASIPin 2, 4, 5: Not used
Weight with batteries kg
0.450
Version Article No.
3RK1904-2AB02
AS-Interface addressing unit V 3.0
• For AS-Interface modules and sensors and actuators with integrated AS-Interface
in accordance with AS-i Specification V3.0
• For setting the AS-i address of standard slaves, and slaves with extended addressing
mode (A/B slaves)
• With input/output test function and many other commissioning functions
• Battery operation with 4 batteries type AA (IEC LR6, NEDA 15)
• Scope of supply:
- Addressing unit with 4 batteries
- Addressing cable, with M12 plug to addressing plug (hollow plug), length 1.5 m
3RK1904-2AB02
Accessories
3RK1902-4PB15-3AA0
Addressing cable, with M12 plug to M12 socket
2)
• For addressing slaves with M12 connection,
e.g. K20 or K60R modules or light curtains
• Length 1.5 m, 3-pole, 3 x 0.34 mm
2
3RK1902-4PB15-3AA0
3RX9801-0AA00
AS-Interface M12 feeders
• Transition of AS-Interface cable to a standard round cable
• Insulation piercing method for connection of AS-Interface cable
• M12 socket for connection of standard round cable
• Current carrying capacity up to 2 A
3RX9801-0AA00
3RK1901-1NR10
AS-Interface M12 feeders
• Transition of AS-Interface cable without U
aux
, with M12 socket
• Insulation piercing method for connection of AS-Interface cable
• M12 socket for connection of standard round cable
3RK1901-1NR10
3RK1902-4HB50-5AA0
M12 cable plug
3)
• Extruded M12 plug (angled cable feeder 90°), other cable end open
• Length: 5 m, 5-pole, color: Black
3RK1902-4HB50-5AA0
3RK1902-4BA00-5AA0
M12 plug straight
3)
• For screw fixing, 5-pole screw terminal, max. 0.75 mm
2
• A-coded, max. 4 A
3RK1902-4BA00-5AA0
Addressing cable, with M12 plug to addressing plug
(hollow plug)
1)
• Included in the scope of supply of the addressing unit
• Length 1.5 m
Z236A
IKPI_04_en.book Seite 148 Montag, 6. Oktober 2014 11:32 11