COMMUNICATIONS / INTERFACES
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2001/2002
4/7 Version C4
A segment can be extended by using RS485 amplifiers.
Recommended: SINEC L2 amplifier for RS 485
(Order No.: 6ES7972-0AA00-0XA0).
In order to guarantee reliable operation of the serial bus
system, the cable must be terminated at both ends using
terminating resistors. It is important to note that when the
drive inverter is in a no-voltage condition, when
(line supply OFF) it is not able to guarantee the power supply
of the bus module / terminating resistor. This means, under
certain circumstances, an active bus terminating device
should be used. (Order No.: 6ES7972-0DA00-0AA0). For
operation at 12Mbd, cables / connectors with integrated
damping network should be used as terminating device.
Furthermore, for 12Mbd operation, a drop cable (spur cable)
from the main bus cable is not permitted.
Suitable SINEC-L2 DP connectors and cables for reliable
operation up to 12Mbd are listed in Table 6:
The floppy disk, supplied together with the PROFIBUS
module, includes the Manual and 2 data files to configure the
associated PLC system.
Brief instructions for setting-up PROFIBUS
communications:
· The bus cable between the master system and drive must
be correctly terminated. This includes the necessary
terminating resistors and (at 12Mbd) the terminating
network.
· The bus cable must be shielded and the shield must be
connected to the housing of the cable connector.
· The PROFIBUS master must be correctly configured so
that communications can be established with a DP slave
using either PPO type 1 or PPO type 3 (only PPO type 1 if
the PPO type has not been configured using remote
operator control).
· When using the COM ET software together with a
SIMATIC S5, the correct descriptive file must be used so
that an IM 308B/C can be configured as bus master. If
the SIMATIC Manager is used for an S7, the object
manager must be loaded.
· The bus must be ready (when using a SIMATIC module,
the operator panel switch must be set to ON).
· The max. bus baud rate is only 12 Mbd.
Order No. Description
6ES7972-0BB10-0XA0 Bus connector with
PG interface
6ES7972-0BA10-0XA0 Bus connector without
PG interface
6ES7901-4BD00-0XA0 Bus cable
Table 6: Order numbers of the connectors and cables
· The PROFIBUS module must be correctly inserted in the
drive inverter and the drive inverter must be connected to
a power source.
· The slave address for the drive (parameter P918) must be
set so that it corresponds to the address configured in the
PROFIBUS master and it must be uniquely defined in the
bus.
PROFIBUS should be installed, carefully maintaining the EMC
guidelines and regulations (these are described in detail in the
Operating Instructions for the drive and the PLC).
Dimensions H x W x D 115 mm x 102 mm x 30 mm
Degree of protection IP 21
Max. bus transfer rate 12 Mbd
Table 7: Technical data
Designation Order No.
PROFIBUS module CB15 6SE3290-0XX87-8PB0
Table 8: PROFIBUS ordering data
Note: The mounting kit for IP56 drive inverters is provided
with each drive inverter and cannot be separately ordered.
Drive 1 Drive 2 Drive 3
Bus cable
Permissible configuration for 12Mbd
Drive 1
Drive 2
Drive 3
Bus cable
Permissible configuration at 12Mbd