P1 Panelboards • Quick reference for selection and application
22
UL 1449 3rd Edition SPD
TPS3 L2 - True 10 Mode Protection
Surge Protection Device (SPD) for Revised P1 Lighting Distribution Panelboards
(for Original P1 – refer to TPS3 L1 Series)
These newly developed kits are for use in the new revised P1 Series only.
Interior part numbers must end with “N” or “T”.
Features:
• Mounts internal to:
– Revised P1 Lighting Panelboards
• Consult factory for field retrofit in Revised P1 Lighting Panelboards
• UL 1449 3rd Edition Recognized
• UL 1283
• Type 4 SPD intended for use in Type 1 applications (Type 2, cUL)
• UL Type 1 tested with all internal OCP and safety coordination
features included
• Large block, individually fused, thermally protected, 50 kA MOVs
• 20 kA In (most models)
• 200 kA SCCR (most models)
• UL96A Lightning Protection Master Label appropriate (@ 20 kA I
n
• Applications
– Provides main service or downstream protection for sensitive computer and
electronic loads
– Standard redundancy use: 150 kA per phase
– Maximum redundancy use: 300 kA per phase
• SPD Specifications
– Directly connected discrete protection elements between all possible modes
providing true 10 mode protection
– Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
150kA 50kA 50kA 50kA 50kA
300kA 100kA 100kA 100kA 100kA
– 100% monitoring (Every MOV is monitored, incl. N-G)
– EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
– Repetitive impulse: 5,000 hits
– Less than ½ nanosecond response time
– Relative humidity range: 1-95% non-condensing
– Operating frequency: 47-63 Hz
– Operating temperature: -25°C (-15°F) to +60°C (140°F)