15
P1 Panelboards • Quick reference for selection and application
Catalog Numbering System
Unassembled Panelboards
Note: Revised P1 was introduced in June 2014. All original P1 devices do not include the "Subfeed Space" Indicator.
All original P1 included the Subfeed Space as standard.
Type of Panel
P1
Voltage and System
X = 208Y/120, 3-Phase 4-Wire
A = 120/240V, 1-Phase 3-Wire
E = 480Y/277V, 3-Phase 4-Wire
7 = xGB interior, 480Y/277V, 3-Phase 4-Wire
Circuits
18, 30, 42, 54* (*Revised P1 only)
Mains MC = Convertible mains
Select Main Lug Kit or Breaker Mounting Kit from page ?
Amperage
400A max (typically 250A or 400A)
Main Bus Material
A = Aluminum
C = Copper
Note:
Standard bussing in P1 panels is tin plated for aluminum and copper.
Standard bus is temperature rated to the maximum amperage in the panel.
Branch Breakers
Panel Type Voltage (Max.) Breaker Type Additional Information
P1, Revised P1
1
240 BL, BLH, HBL, BQD, NGB, HGB, LGB
See Page 17
480 / 277 BQD, NGB, HGB, LGB,
600 / 347
3
BQDG
2
, NGB, HGB, LGB
1 ConsultsalesofceforavailabilityofCSA.
2 See Speedfax for additional information.
3 600/347V options are not available in a UPB panel - see factory assembled section.
Type P1 unassembled panelboards are
completely convertible from main lug
to main breaker and vice-versa.
Additionally feed-thru lugs, or subfeed
circuit breakers up to 400 ampere can
be added without increasing the box
height for Revised P1 with “T” suffix,
see the chart.
1. Compute total number of poles to
determine interior catalog number.
(Note: BL / BQD (or) xGB Main Breaker
will use unit space. The total number of
poles should include 2 (or) 3 poles for
1-phase (or) 3-phase mains.)
2. List catalog number and price of
interior, box and front.
3. Select main lug kit or main breaker
kit from appropriate tables.
Note: Main/Subfeed Breaker mounting
kits may be ordered with or without
breakers included, see page 5
and 6 for selection.
4. List required branch circuit
breakers and filler plates to cover
any unused positions.
5. Select any modifications
or accessories.
P 1 X 1 8 M C 2 5 0 A T
Subfeed Space Indicator (for Revised P1 only)
T = Subfeed Space Included