P1 Panelboards • Quick reference for selection and application
20
TPS3 02
Surge Protection Device (SPD) for Revised P1 Lighting Panelboards
(for Original P1 – refer to TPS3 01 Series)
UL 1449 3rd Edition SPD
These newly developed kits are for use in the new revised P1 Series only.
Interior part numbers must end with “N” or “T”.
Features:
• Mounts internal to:
– Revised P1 Lighting Panelboards
• Consult factory for field retrofit in Revised P1
Lighting Panelboards
• UL 1449 3rd Edition Recognized
• UL 1283
• Type 4 SPD intended for use in Type 1 applications (Type 2, cUL)
• UL Type 1 tested with all internal OCP and safety coordination
features included
• Large block, individually fused, thermally protected, 50 kA MOVs
• 20 kA I
n
(most models)
• 200 kA SCCR (most models)
• UL96A Lightning Protection Master Label appropriate (@ 20 kA I
n
)
• Applications
– Provides main service or downstream protection for sensitive
computer and electronic loads
– Standard redundancy use: 100 kA per phase
– Increased redundancy use: 200 kA per phase
– Maximum redundancy use: 300 kA per phase
• SPD Specification
– Surge Current Rating Per Phase
Per Phase L-N L-G N-G
100kA 50kA 50kA 50kA
150kA 100kA 50kA 50kA
200kA 100kA 100kA 100kA
250kA 150kA 100kA 100kA
300kA 150kA 150kA 150kA
– 100% monitoring (Every MOV is monitored, incl. N-G)
– EMI/RFI filtering: Active tracking up to -50 db from 10 kHz to 100 MHz
– Repetitive impulse: 5,000 hits
– Less than ½ nanosecond response time
– Relative humidity range: 1-95% non-condensing
– Operating frequency: 47-63 Hz
– Operating temperature: -25°C (-15°F) to +60°C (140°F)