6/176
Siemens IK PI · 2015
Industrial Wireless Communication
WirelessHART
SITRANS AW210 WirelessHART adapter
■
Technical specifications
Input
Point-to-point connection to a HART
field device or
Point-to-point connection to a
4 ... 20 mA field device or
Up to eight HART field devices with
an external voltage supply integrated
using multidrop
Communication
• HART communication with multi-
drop, as primary or secondary
HART master (can be specified)
• 4 ... 20 mA current signal with a
point-to-point connection scaling in
user-defined measuring range in
SITRANS AW210
- Linear
- User-defined scaling with
up to 32 points
Protocol
HART V7
(compatible with previous HART
versions)
Output
Communication WirelessHART V7
Transmission frequency band
2.4 … 2.4835 GHz (ISM band),
16-channel frequency hopping
spread spectrum
Range (under reference conditions)
Outside up to 235 m (771.00 ft)
RF signal strength
10 dBm
Output signals
• WirelessHART adapter •HARTCmd3
Measured current and up to 4 other
dynamic variables (measured
values, derived values) or device
variables
•HARTCmd9
Up to 8 dynamic variables with
status
•HARTCmd48
Additional status information
• 4 ... 20 mA field device
Scaled or linearized process values
• HART field device
•HARTCmd3
Measured current and up to 4 other
dynamic variables (measured
values, derived values) or device
variables
•HARTCmd9
Up to 8 dynamic variables with
status
•HARTCmd48
Additional status information
Update time for output signals You can set the update times
separately for the adapter and the
connected devices.
The possible settings are:
• 1, 2, 4, 8, 16, 32 s
• 1, 2, 5, 10, 30, 60 min
(times also depend on the gateway)
Measuring accuracy
Max. measuring error
(4 ... 20 mA circuit)
1 % of measuring range,
40 … 85 °C (104 … 185 °F)
Rated conditions
Location Outside/inside
Ambient conditions
• Ambient temperature -40 ... +85 °C (-40 ... +185 °F)
In hazardous areas
up to 75 °C (167 °F)
• Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
Electromagnetic compatibility
To EN 301 489-17 and EN 300 328-1
Design
Weight 0.46 kg (1.01 lb)
Enclosure
• Material Enclosure:
Aluminum alloy, RoHS-compliant
polyurethane corrosion-resistant
coating
Cap:
Resin
• Cable entry
½" NPT female thread
Degree of protection
IP68
Aerial Potted in enclosure
Auxiliary power
Power supply Loop power 1 … DC 2.5 V,
can be set by user
in 0.5 V DC increments
Loop-powered, operating current
DC 3.2 … 25 mA operating current;
overvoltage, surge and reverse
polarity protection
Certificates and approvals
Wireless communication approvals • CE (R&TTE, EMC)
• FCC Part 15.247 for wireless
applications in the 2.4 GHz trans-
mission frequency band
•IC
Kap_06_IWC_en.book Seite 176 Dienstag, 7. Oktober 2014 1:47 13
© Siemens AG 2014
Comentarios a estos manuales