Configuration Using Web Based Management and the Command Line Interface
Configuration
C79000-G8976-C184-07
217
Select the iPCF Enabled check box to enable the iPCF mode.
CE W788-xRR models, you can also set optimized support of
PNIO upda
When setting the update time, make sure that you note the following situations
ill not be able to establish stable communication:
Case a: Your system operates in a single cell; in other words the clients
links, SCALANCE W74x) do not need to support roaming to another
update tim
ur system o fferent cha
In this case, update tim ms are supported.
Case c: Your system operates with several cells and with more than 2 channels
and the clients roam between cells.
In this case, the PN IO update time should be set higher than 16 ms.
Notice
We strongly advise that you check the local wireless characteristics prior to
commissioning.
With the SCALAN
PNIO if you select the PNIO support enabled check box. In this case, you must
also set the PNIO update time. The PNIO update time must match the configured
PNIO update time.
te times
otherwise there is a risk that you w
(IWLAN/PB
cell.
In this case, es >= 8 ms are supported.
Case b: Yo perates with two cells on two di
es >= 16
nnels.
Operating Instructions SCALANCE W78x