Page 82 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
Parameters
P907 Programmer Interface
Press ENTER
to activate the programmer interface (two way infrared
communications) test.
On successful test completion, PASS is displayed. Otherwise, FAIL is displayed.
P910 Relay
Access this parameter to display the current state of the specified relay.
Press ENTER to alter the relay state (energized / de-energized) or enter the value
corresponding to the specific relay state desired.
P911 mA Output Value
Access this parameter to display the current value of the mA output.
Additionally, this feature may be used to enter a desired value. The mA output
immediately assumes the value entered regardless of any restrictions programmed.
P912 Transducer Temperature
Use this feature to display the temperature in °C (as monitored by the connected
transducer).
Err is displayed if the transducer is not equipped with an internal temperature sensor.
P913 Sensor Temperature
Access this parameter to display the temperature in °C (as monitored by the TS-3).
OPEn is displayed if a TS-3 is not connected.
Values
0 = de-energized
1 = energized
Primary Index mA output
Values Range: 0.00 to 25.00
Related
P200 mA Output Range
P201 mA Output Function
Values Range: -50 to 150
Values Range: -50 to 150