SIMATIC S7-400
Function modules
FM 458-1 DP application module
EXM 438-1 input/output expansion
6/94
Siemens ST 70 · 2013
■
Technical specifications (continued)
Encoder signals, incremental encoder
(asymmetrical)
• Trace mark signals Track A and B (phase-shifted by
90 degrees), possibly with zero
pulse N
• Input voltage
with 0 signal: -30 to +4 V
(at 15 mA load); with 1 signal:
+8 to 30 V (at 15 mA load);
permissible input voltage range:
differential voltage -30 to +30 V
Encoder signals, absolute encoder
(SSI)
• Input signal 5 V acc. to RS 422
• Data signal
Dual-, Gray-, Gray-Excess-Code
• Clock frequency, max.
2 MHz; 100 kHz to 2 MHz
(depending on cable length)
Errors/accuracies
Linearity error (relative to output area) (+/- 1 LSB )
Galvanic isolation
Galvanic isolation digital inputs
• Galvanic isolation digital inputs No
Galvanic isolation digital outputs
• Galvanic isolation digital outputs No
Galvanic isolation analog inputs
• Galvanic isolation analog inputs No
Galvanic isolation analog outputs
• Galvanic isolation analog outputs No
Dimensions
Required slots 1
Weight
Weight, approx. 1kg
6DD1 607-0CA1
■
Ordering data
Order No.
EXM 438-1
input/output expansion
6DD1 607-0CA1
For direct exchange of digital
and analog signals between
FM 458-1 DP and the plant
SB10 interface module 6DD1 681-0AE2
To connect 8 binary inputs or
outputs to FM 458-1 DP
SB61 interface module 6DD1 681-0EB3
To connect 8 binary inputs to
FM 458-1 DP, input voltage:
24/48 V DC
SB71 interface module 6DD1 681-0DH1
To connect 8 binary outputs to
FM 458-1 DP, output voltage:
24/48 V DC
SU12 interface module 6DD1 681-0AJ1
To connect 10 signals to
FM 458-1 DP
SU13 interface module 6DD1 681-0GK0
To connect 50 signals to
FM 458-1 DP
SC 62 interface cable 6DD1 684-0GC0
To connect EXM 438-1
with up to 5 SBxx or SU12
SC 63 interface cable 6DD1 684-0GD0
To connect EXM 438-1 with an SU13
Kap_06_eng.book Seite 94 Donnerstag, 2. Mai 2013 4:16 16