Siemens Simatic M7-400 Manual de usuario Pagina 13

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 158
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 12
SIMATIC S7-400
Central processing units
Standard CPUs
CPU 416
6/13
Siemens ST 70 · 2013
6
Overview
High-performance CPUs in the high-end performance range
Applicable for plants with high requirements in the high-end
performance range
Integrated PROFINET functions in CPU 416-3 PN/DP
Technical specifications
6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0
CPU 416-2 CPU 416-3 CPU416-3 PN/DP
General information
Engineering with
Programming package STEP7 V 5.3 SP2 or higher
with HW update
STEP7 V 5.3 SP2 or higher
with HW update
STEP7 V5.5 or higher/iMap V3.0 +
iMap STEP7 Add-on V3.0 SP5 or
higher
Supply voltage
24 V DC No; Power supply via system power
supply
No; Power supply via system power
supply
No; Power supply via system power
supply
Power losses
Power loss, typ. 4.5 W 5.5 W 6.5 W
Memory
Work memory
• integrated 5.6 Mbyte 11.2 Mbyte 16 Mbyte
integrated (for program)
2.8 Mbyte 5.6 Mbyte 8Mbyte
integrated (for data)
2.8 Mbyte 5.6 Mbyte 8Mbyte
Load memory
• expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte
integrated RAM, max.
1Mbyte 1Mbyte 1Mbyte
• expandable RAM, max.
64 Mbyte 64 Mbyte 64 Mbyte
CPU processing times
for bit operations, typ. 30 ns 30 ns 30 ns
for word operations, typ. 30 ns 30 ns 30 ns
for fixed point arithmetic, typ.
30 ns 30 ns 30 ns
for floating point arithmetic, typ. 90 ns 90 ns 90 ns
Counters, timers and
their retentivity
S7 counter
•Number 2 048 2 048 2048
IEC counter
•present Yes Yes Yes
S7 times
•Number 2 048 2 048 2048
IEC timer
•present Yes Yes Yes
Kap_06_eng.book Seite 13 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Vista de pagina 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 157 158