SIMATIC S7-400
Communication
Loadable drivers for CP 441-2 and CP 341
6/106
Siemens ST 70 · 2013
6
Overview
Drivers for Modbus protocol with RTU message format;
communication as master or slave
Downloadable onto CP 341 and CP 441-2
(6ES7 441-2AA04-0AE0)
Technical specifications
Parameterization software Loadable drivers
for CP 441-2 and CP 341
Type of license
Simple license, copy license
Target system SIMATIC CP 341, SIMATIC CP 441-2
Technical specifications
Modbus Master
Modbus protocol with RTU format
Master/slave coupling:
SIMATIC S7 is master
• Function codes implemented:
01, 02, 03, 04, 05, 06, 07, 08,
11,12,15,16
• No V.24 control and signal lines
CRC polynomial: x
16
+ x
15
+ x
2
+1
• Interfaces: TTY (20 mA);
V.24 (RS 232 C);
X.27 (RS 422/485)
2-wire or 4-wire
Receive mailbox specified on
BRCV
Character delay time
3.5 characters or multiple thereof
Broadcast message possible
Adjustable parameters Transmission rate 300 bit/s up to
76800 bit/s (TTY up to 19200 bit/s)
Character frame
With/without RS 485 operation
for 2-wire connections
With/without modem operation
(ignore smudge characters)
Response monitoring time 100 ms
to 25.5 s in steps of 100 ms
• Factor for the character delay
time 1-10
Default setting of receive line when
using the X.27 interface module
Modbus slave
Modbus protocol with RTU format
Master/slave coupling:
SIMATIC S7 is slave
Function codes implemented: 01,
02, 03, 04, 05, 06, 08, 15, 16
No V.24 control and signal line
CRC polynomial: x
16
+ x
15
+ x
2
+1
• Interfaces: TTY (20 mA),
V.24 (RS 232C),
X.27 (RS 422/485)
2-wire or 4-wire
Communications FB 180, instance
DB 180 (use of a multi-instance)
Conversion of the Modbus data
address to S7 data areas. Data ar-
eas which can be processed: DB,
bit memories, outputs, inputs, tim-
ers, counters
Character delay time
3.5 characters or multiple thereof
Adjustable parameters
Transmission rate 300 bit/s up to
76800 bit/s (TTY up to 19200 bit/s)
Character frame
Slave address of CP (1 to 255)
With/without RS 485 operation
for 2-wire connection
With/without modem operation
(ignore smudge characters)
Factor for the character delay
time 1-10
• Number of work DB
(for FB processing)
Enabling of memory areas
for writing by the master
Default setting of receive line when
using the X.27 interface module
Conversion of Modbus addresses
to S7 data areas
Kap_06_eng.book Seite 106 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013