Section 3 Configuration S800 I/O Configuration - Basic Rules and Examples
3BSE056248 33
Non-redundant PROFIBUS Node
In total max 24 modules per CI801 but limited by:
PROFIBUS data capability.
CI801/TB820 Power supply capability.
Required scan cycle time.
Modules not supported:
DI825, DO880, AI880A, DI830, DI831, DI880, DI885.
5 Mbit/s ABB Drives and SOE on DI840 are not supported.