Communication Interface Section 1 Product Overview
12 3BSE056248
Communication Interface
A number of communication modules can be connected to the controller. See
Appendix A, IndustrialIT System 800xA AC 800M Controller - Data Sheet for
more information on the various modules.
Communication Interface connected with CEX bus:
Up to 12 communication units can be placed on Communication Expansion Bus
(CEX) bus.
The CEX bus must be terminated if a communication unit is connected. A CEX bus
termination is delivered with the e CPU: tb850 (male) or TB851 (female).
An extension cable TK850 with connector DB25P with metal housing and a length
of 0.7meter (1.3') can be used for extending the CEX bus to a second din rail.
S800 I/O
S800 I/O is a distributed and modular I/O system that communicates with
controllers over PROFIBUS-DP/DPV1 or direct (via Modulebus).
The S800 I/O system is DIN rail mounted and consists of Fieldbus Communication
Interfaces, Modulebus Modems, S800 I/O modules and Module Termination Units
(MTU). S800 I/O modules (not S800L) are mounted on MTU's, this makes them
hot-swappable. Depended on the mounting requirement (horizontal or vertical) and
on the field termination needs (powering, fusing etc.) there are numerous of MTU's
to choose from.
The S800 I/O system supports fully redundant applications, redundancy can be built
in on both communication level and I/O module level.
S800 I/O connected with PROFIBUS- DP/DPV1:
• Field Communication Interface CI801 or CI840 is the I/O station master
• Maximum 24 I/O modules per I/O station
• 1 base I/O cluster with up to 12 I/O modules (connected via electrical
Modulebus)
• 1-7 additional I/O clusters with up to 12 I/O modules per cluster (connected via
optical Modulebus using Modulebus Modems)