A AS-Interface Protocol Implementation Conformance Statement (PICS)
118
CP 343−2 / CP 343−2 P AS−Interface Master
Release 08/2008
C79000−G8976−C149−04
Table K-2 PICS, (continued)
No. Comment / Function implemented byM4Function or Call on the Host Interface
(symbolic representation)
6 Support of Combined transaction type 4
integrated
X
7 Support of Combined transaction type 5
integrated
X
How the AS-i cycle time depends on the number of connected slaves
The AS-i cycle time can be calculated using the following formula:
If 5 or more AS-i slaves are activated:
t
cycl
= (1 + number of activated AS-i slaves) x 154 ms
If less than 5 AS-i slaves are activated:
t
cycl
= (1 + number of activated AS-i slaves) x 654 ms
Note
If two 2 AS-i slaves with extended addressing mode occupy the same address (for
example, address 5A and address 5B), this slave pair is calculated as one 1 AS-i
slave in the above formula. The reason for this is that slave pairs with the same
address are addressed only in every second cycle. The cycle time in the formula
above is therefore doubled for such slaves.
-