7 Dealing with Problems / Error Displays
114
CP 343−2 / CP 343−2 P AS−Interface Master
Release 08/2008
C79000−G8976−C149−04
Table 10-1 , continued
Error RemedyPossible Cause
The replaced AS-i slave is not cor-
rectly connected or is defective.
Check the connections of the
slave and if necessary replace the
slave.
The “CER” LED and the LEDs of
active AS-i slaves flicker irregu-
larly.
An extender is installed in the AS-
interface with “Line1” and “Line2”
and the connections are reversed.
Correct the connections on the
extender.
-