Figure 13
Once in NetPro, select the CPU and double click on the first line in the table below. This will open a window
to insert a new connection (Figure 14).
Figure 14
Make sure Unspecified is selected and the connection type is S7, then click OK.
A property window for the S7 connection pops up. Enter the following information as shown in figure 15:
1. Make sure “Establish an active connection” is NOT checked; this makes the PLC the Server.
2. Make sure the Interface selected is CP 343-1.
3. Enter the Partner name (any name works), in this example G306. The partner is the device the S7
will create a connection.
4. Enter the Partner IP address, in this example 192.168.200.10.