Siemens SIMATIC NET Manual de servicio Pagina 89

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 150
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 88
Command Interface
5-21
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
5.2.9 Get_Extended_Actual_Configuration
Purpose of the Command
With this call, the following configuration data of an addressed AS-i slave obtained
by the AS-i master on the AS-Interface are read.
I/O configuration
ID code
Extended ID1 code
Extended ID2 code
The configuration data are specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the Job Data in the Send Buffer
Bank Byte Meaning
Bit 7 Bit 4 Bit 3 Bit 0
2 0 Command number 28
H
2 1 Slave address
Structure of the Job Data in the Receive Buffer
Bank Byte Meaning
Bit 7 Bit 4 Bit 3 Bit 0
2 0 Echo of the command number: 28
H
2 1 Command status
2 2 ID code I/O configuration
2 3 Extended ID1 code Extended ID2 code
Vista de pagina 88
1 2 ... 84 85 86 87 88 89 90 91 92 93 94 ... 149 150

Comentarios a estos manuales

Sin comentarios