Siemens REV-R.03/1 Manual de usuario Pagina 7

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 8
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 6
7 / 8
Siemens Electromotoric actuators CE1N4540en
Building Technologies 05.11.2009
G
G0
YR
SP
SN
Y...
DC 0...10 V
N1
2
4
V
M
R1
RM MR
F1
0...1000 Ω
Y1
4540A01
U
P1F2
1 32
ϑ
N1 Controller
Y1 Actuator
R1 Signal indicator with 0…1000 output
F1 Frost protection monitor with 0…1000 output
F2 Frost protection thermostat
Terminal: 1 – 3 frost hazard / sensor is interrupted (thermostat closes with frost)
1 – 2 Normal operation
P1 Position feedback DC 0…10 V
SP System potential AC 24 V
SN System neutral
If a device is connected to terminal R, the factory-fitted bridge across R – M on the
printed circuit board must be cut through.
U
M
R
4573Z06
Y
G
G
0
Position indicator DC 0…10 V
Measuring neutral (= G0)
Signal input 0…1000 Ω
Signal input DC 0…10 V (SQS65.2: DC 2…10 V)
Operating voltage AC 24 V: system potential SP
Operating voltage AC 24 V: system potential SN
Dimensions
Dimensions in mm
60 68
128
28 88
120
1
3
4
M30x1,5
80
32
111*
ø20.5
(M20)
4540M01
*
Height of actuator after fitting on valve
> 100 mm Minimum clearance from wall or ceiling
> 200 mm for mounting, connection, operation, service etc
SQD65
Note
Connection terminals
SQD65