If you are using one of the recommended
protocol converters from Anybus, Merrick has
an adapter board (Part No M22787-1) that
connects to the DB9-S connector and offers
screw terminals for the cable.
When you have connected and powered up,
check that all looks OK in the ModBus
Diagnostic screen. See page 8.
Troubleshooting tips
Setting up industrial networks can sometimes be a daunting task. In this example, you may have
to deal with several mapping layers and communication protocols. Fortunately, there are excellent
troubleshooting tools available.
Look at the LED's on the GCM board.
The transmit (GCM sending) LEDs are red, and the receive LEDs are green. No receive activity
indicates cable or host problems. No transmit activity indicates addressing or serial parameter
problems
Transmit
Receive
Port 1
Transmit
Receive
Port 2
Check Data in the TCMI CIT Diagnostic Screen.
The TCMI CIT Diagnostic Screen (P1) displays data in the CIT as it is received and transmitted
over the Modbus port.