Siemens GC..M.. Manual de usuario Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 11
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
http://www2.merrick-inc.com/mct/GCMModbus.pdf Page 11 2014-05-18/Lars
WaiEnd
Counter for ModBus RTU and UISServer telegrams who have had the end condition
determined by absence of incoming characters for enddl (see below) 5 ms ticks.
enddl
Min wait in in 5 ms ticks for absence of incoming characters to determine end
condition.
Note 1. Rxlfm indicates what kind of format error occurred last, as rxfme increments. In some
cases, a NAK response is sent back to the master/client. This is indicated in the
following table with a numerical value. An “x” indicates that the telegram will be ignored
for the format error. An empty field indicates that the specific format error does not
apply for this protocol.
Rxlfm
ASCII
RTU
Format error
1
x
x
Illegal receiver buffer length
2
x
Illegal characters in telegram Modbus ASCII only
3
Not used in Modbus
4
3
3
Function 3 telegram not 8 bytes
5
Not used in Modbus
6
1
1
Unknown/Unsupported Function
7
3
3
Byte count disagrees with buffer length Function 16
8
3
3
Byte count disagrees with length field Function 16
9
Not used in Modbus
10
x
Illegal end sequence: LF not following CR Modbus ASCII only
11
x
x
ISR Receiver buffer overrun
12
x
x
ISR Transmitter buffer overrun
13
x
x
ISR Characters received after end of message, before reply sent
14
x
x
ISR Illegal (default) receiver state (COMrxsta)
15
2
2
Outside CIT legal read space on CIT read or write
16
1
1
Unsupported subfunction for function 8 telegram
17
3
3
Function 8 telegram not 8 bytes
18
2
2
Write to read-only space in CIT
19-33
Not used in Modbus
34
x
Transmitter length rollover Should never happen
35
x
Receiving characters while transmitting
Use the integrity bit.
In the PLC, toggle the integrity bits (Word 44, bit 7) every 2 seconds. Monitor the integrity echo bit
(Word 16 bit 7). If they stop toggling, communications has failed, and appropriate steps can be
taken. The integrity bit can be monitored in the TCMI CIT Diagnostic Screen (P1), and the GCM
can be set up to monitor the activity of the integrity bit, potentially generating a Warning or Fault if
the bit stops toggling.
PLC Program examples.
There are plenty of PLC example programs available in the Merrick MCT web site. See
http://www2.merrick-inc.com/mct/.
Vista de pagina 10
1 2 ... 6 7 8 9 10 11

Comentarios a estos manuales

Sin comentarios