Siemens PLT 111 · 1999
4/5
I/O modules
Function modules
Closed-loop control modules
Function modules
Function modules have their own functions which are indepen-
dent of the central unit. They possess backup modes which per-
mit operation independent of the central unit.
Some of the function modules are configurable. The firmware of
these configurable modules contains an interpreter which pro-
cesses a user configuration made up of defined blocks. This
user configuration is generated on a personal computer using
the STEP M (BG) programming language, loaded into the mod-
ule via a serial TTY interface, and stored in an EEPROM. The
STRUK-AS 220 EA program is used as the configuring aid for
this purpose (see page 4/9).
1)
Closed-loop control modules
Three different S and K closed-loop control modules are avail-
able:
S closed-loop control module, with 2 PI controllers S,
6DS1 402-8BA
Two-channel, autonomous PI closed-loop controller. Can be
used as a fixed setpoint controller in SPC, DDC and backup
modes. In backup mode, the controller can be operated using
controls on the front panel.
The module detects 3 analog signals and a position feedback
per channel.
S closed-loop control module, two-channel, configurable,
6DS1 411-8RR
Two-channel, autonomous controller which acts directly on the
process via power control units. The manipulated variable sig-
nal is a stepped output.
The module can be used to implement 2 independent controls
(individual controls) or 2 associated controls (master controls)
by appropriate configuring.
The closed-loop control module must be configured. The PC is
connected via the front plug of the module.
1)
K closed-loop control module, with 2 PI controllers K,
6DS1 403-8CB
Two-channel, autonomous PI closed-loop controller. Can be
used as a fixed setpoint controller in SPC, DDC and backup
modes. In backup mode, the controller can be operated using
controls on the front panel.
The module detects 3 analog signals and a position feedback
per channel. The input signals can be monitored in live-zero
mode according to the NAMUR NE 43 recommendation.
K closed-loop control module, two-channel, configurable,
6DS1 412-8RR
Two-channel, autonomous controller which acts directly on the
process via power control units. The manipulated variable sig-
nal is a continuous output.
The module can be used to implement 2 independent controls
(individual controls) or 2 associated controls (master controls)
by appropriate configuring.
The closed-loop control module must be configured. The PC is
connected via the front plug of the module.
1)
1) With AS 235 systems, STRUK-AS 220 EA (page 4/9) can also be used for
operations via the CS 275 plant bus (software release G and later)
Ordering data Order No.
Calculation modules
Binary calculation module, configurable,
6DS1 717-8RR, and
binary extension module, 6DS1 719-8RR
Autonomous module for binary logic operations. Application
examples:
– Individual control drive (max. 5 channels)
– 2-out-of-3 selection with switching off of faulty channel
– Limit formation
– Protective and release interlocks
– Unit switchover.
The calculation module must be configured. The PC is con-
nected via the front plug of the module.
1)
The binary extension module 6DS1 719-8RR can be connected
in order to increase the number of binary signal inputs and out-
puts.
Ordering data Order No.
Closed-loop control modules
S closed-loop control module,
with 2 PI controllers S
– Module
– German Instruction Manual
– English Instruction Manual
6DS1 402-8BA
C79000-B8000-C17
C79000-B8076-C17
S closed-loop control module,
two-channel, configurable
– Module
– German Instruction Manual
– English Instruction Manual
6DS1 411-8RR
C79000-B8000-C258
C79000-B8076-C258
K closed-loop control module,
with 2 PI controllers K
– Module
– German Instruction Manual
– English Instruction Manual
6DS1 403-8CB
C79000-B8000-C298
C79000-B8076-C298
K closed-loop control module,
two-channel, configurable
– Module
– German Instruction Manual
– English Instruction Manual
6DS1 412-8RR
C79000-B8000-C257
C79000-B8076-C257
Calculation modules
Binary calculation module,
configurable
– Module
– German Instruction Manual
– English Instruction Manual
6DS1 717-8RR
C79000-B8000-C129
C79000-B8076-C129
Cable, for connection of
– 1 extension module
– 2 extension modules
– 3 extension modules
– 4 extension modules
6DS9 925-8AA
6DS9 925-8AB
6DS9 925-8AC
6DS9 925-8AD
Binary extension module,
for binary calculation module
6DS1 719-8RR
(additional order code: G1A)
Instruction Manual
Binary extension module
– German
– English
C79000-B8000-C130
C79000-B8076-C130