SED2 variable speed drivesOperating instructionsCM1U5192en01.2002Siemens Building TechnologiesHVAC Products

Pagina 2 - HVAC Products 01.2002

10/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.2002

Pagina 3 - Table of contents

100/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2221[2].P2222[2],P2223[2]BI: Fixed PID set

Pagina 4

101/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Unit: % Min: - Def: - Max: -Note:r2250=100

Pagina 5

102/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Note:It is essential that you select the co

Pagina 6

103/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2303[2] CI: PID o/p offsetSelects the sour

Pagina 7 - 1 Introduction

104/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2378 Staging frequency f, %fMaxThe frequen

Pagina 8 - 1.6 Document conventions

105/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.6 Overview of factory and user parameter

Pagina 9

106/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Continued: Overview of factory and user par

Pagina 10

107/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Troubleshooting 01.20027 Troubleshooting7.1 Troubleshooting us

Pagina 11 - 2 Safety instructions

108/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Troubleshooting 01.20027.2 Error messages7.2.1 Error code list

Pagina 12 - 2.4 Repairs

109/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Troubleshooting 01.2002Error Cause Diagnosis & Remedy Reac

Pagina 13 - 3 Mechanical installation

11/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Safety instructions 01.20022 Safety instructionsThe following w

Pagina 14 - 3.3 Mounting

110/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Troubleshooting 01.2002Error Cause Diagnosis & Remedy Reac

Pagina 15

111/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Troubleshooting 01.20027.2.2 Warning code listsError Cause Dia

Pagina 16

112/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Troubleshooting 01.2002Error Cause Diagnosis & Remedy Reac

Pagina 17 - 5192M01en

113/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Technical data for the SED2 01.20028 Technical data for the SE

Pagina 18

114/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Technical data for the SED2 01.2002Min. input current: 6 mA (a

Pagina 19 - 4 Electrical installation

115/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Technical data for the SED2 01.2002IP54 / NEMA 12Framesize WxH

Pagina 20

116/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Technical data for the SED2 01.2002200 V to 240 V, ± 10%, 3 ph

Pagina 21 - Torx driver T20

117/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Technical data for the SED2 01.2002380 V to 480 V, ± 10%, 3 ph

Pagina 22 - Torx screwdriver

118/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Technical data for the SED2 01.2002500 V to 600 V, ± 10%, 3 ph

Pagina 23 - SPS: Programmable controllers

119/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Appendix 01.20029 Appendix9.1 OptionsDepending on the applicat

Pagina 24 - Cable routing for frame

12/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Safety instructions 01.2002The following terminals may carry da

Pagina 25 - Incoming mains voltage

120/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Appendix 01.20029.1.1 Retrofitting EMC filters for VSD frame s

Pagina 26

121/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Appendix 01.20029.3 List of abbreviationsAlternating current.A

Pagina 27 - Removing the cover of the

122/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Appendix 01.2002For pumps (or fans): The process of starting a

Pagina 28 - Frame sizes D and E

123/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Index 01.2002IndexAabbreviations...

Pagina 29 - FramesizeF

124/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Index 01.2002motor overload protection...

Pagina 30 - (Ground)

125/126Siemens Building Technologies SED2 variable speed drives CM1U5192enLandis & Staefa Division Index 01.2002

Pagina 31 - L3 U V WL2L1

126/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products 01.2002Siemens Building Technologies Ltd.HVAC ProductsGubelstr

Pagina 32 - Access to the mains

13/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Mechanical installation 01.20023 Mechanical installation3.1 Ins

Pagina 33

14/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Mechanical installation 01.2002Do not install the VSD in an env

Pagina 34 - EMC filter

15/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Mechanical installation 01.20023.3.1.2 Dimensions of SED2 footp

Pagina 35 - 1 (17) 10 (7) 1 (17) 10 (7)

16/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Mechanical installation 01.20023.3.2 Dimensions of SED2 drives

Pagina 36 - 4.3.9 Direction of rotation

17/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Mechanical installation 01.20023.3.3 Mounting SED2 drives with

Pagina 37 - 5192Z11en

18/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Mechanical installation 01.20023.3.4 Mounting SED2 drives with

Pagina 38 - 4.4 Control terminals

19/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024 Electrical installationThe VSD

Pagina 39 - 4.5 SED2 block diagram

2/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products 01.2002

Pagina 40

20/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002LK 700125192Z01Disconnecting the

Pagina 41 - 5 Commissioning

21/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20021235192Z0220 21 22 23 24 2529 30

Pagina 42 - 5.1.1 DIP switch settings

22/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.1.3 Operation with a residual

Pagina 43 - ≥ motor rating?

23/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.2 EMC-compatible installationT

Pagina 44

24/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002L1L2L3PEwvu5192Z04enMin. 16 mm²(

Pagina 45 - Function Effects

25/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002Shield connectedwith tube clipsM

Pagina 46 - 5.4 Commissioning modes

26/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.3.1 Access to connection termi

Pagina 47

27/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.200215192J2024.3.2 Access to connect

Pagina 48

28/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.3.3 Access to connection termi

Pagina 49 - Resulting display

29/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.200223415192J1456Opening the housing

Pagina 50 - 5.4.7 10 Hz test

3/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.2002Table of contents1 Introduction ...

Pagina 51 - 5.4.8 General operation

30/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.3.4 Power and motor terminals:

Pagina 52

31/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002DC+DC+DC+DC- B-R+ B+ B+L3 U V WL

Pagina 53 - 6 Programming

32/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.200223415192J1456Access to the mains

Pagina 54 - See AOP operating

33/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024x5192J186x5192J19

Pagina 55 - 6.3.1 Digital inputs

34/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002PE L1 L2 L3L1DC+BDC+BUVL2 L3 WDC

Pagina 56 - DIN2 DIN1

35/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002Input voltage range 200 V – 240

Pagina 57 - 6.3.2 Analog inputs

36/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002Input voltage range 500 V – 600

Pagina 58 - Time in ms

37/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.3.10 Star or delta connectionT

Pagina 59

38/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.4 Control terminalsUse only sh

Pagina 60 - 6.3.3 Analog outputs

39/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.20024.5 SED2 block diagramL1L2L3B-Fi

Pagina 61

4/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.20024.3.5 Power connection for drives with a bui

Pagina 62

40/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Electrical installation 01.2002

Pagina 63 - 6.3.8 Communication

41/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025 CommissioningWarningsOnly authorized per

Pagina 64 - CONTROLLER

42/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.1.1 DIP switch settingsFor all versions

Pagina 65 - 5192Z22en

43/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.2 Checklist prior to startWhatüüüüIs the

Pagina 66 - 5192D01en

44/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.3.2 Description of the advanced operator

Pagina 67 - 5192Z23en

45/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.3.4 Buttons and their functions on the o

Pagina 68 - 6.4.4 Staging pumps or fans

46/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.4 Commissioning modes5.4.1 Overview of c

Pagina 69 - Demand or volume flow

47/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.2002Quick commissioning flow chart1)Motor-spec

Pagina 70

48/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.4.3 Motor data for parameterization5.4.4

Pagina 71 - 5192D04en

49/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.20025.4.4.2 Setting parameters with the BOP or

Pagina 72

5/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.20026.3.3 Analog outputs ...

Pagina 73 - 6.4.6 Bypassing the VSD

50/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.2002"Busy" signalIn some cases, the

Pagina 74 - P1264 P1262 P1262P1263

51/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.2002Testing with the AOP1. Restore the factory

Pagina 75 - 6.4.7 Hibernation mode

52/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Commissioning 01.2002

Pagina 76

53/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026 Programming6.1 Introduction to the SED2 sy

Pagina 77

54/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.2.3 Diagram for a parameter overviewL1L2L3

Pagina 78

55/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.3 Basic functions of the SED26.3.1 Digital

Pagina 79

56/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Setting 99 (BICO) is intended for experience

Pagina 80

57/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Example of the display while testing the inp

Pagina 81

58/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002InputtypeSCALInputADCdeadbandDelayLoss of si

Pagina 82 - P0508[4] Unit

59/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002ymaxy2(P0760)y1(P0758)x1(P0757)x2(P0759)%VmA

Pagina 83

6/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.2002

Pagina 84

60/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.3.3 Analog outputsThe analog outputs prima

Pagina 85

61/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002r0774Shows the analog output value (in V or

Pagina 86

62/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P0781Defines the DAC dead zone for the analo

Pagina 87

63/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.3.6 OFF functionsThis command (by eliminat

Pagina 88

64/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.4 HVAC functions of the SED2The functions

Pagina 89

65/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P0757[1] to P0760[1]Set the scaling of the a

Pagina 90

66/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Torque [Nm]Frequency [Hz]Threshold frequency

Pagina 91

67/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20024. Set the alarm delay parameter P2192:P2192

Pagina 92

68/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20024. Set the desired reaction of drive belt fa

Pagina 93

69/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002If MV runs at maximum frequency and the PID

Pagina 94

7/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.20021 Introduction1.1 Purpose of this documentTh

Pagina 95

70/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002As a rule, the factory settings can be used.

Pagina 96

71/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2378Staging frequencyThis parameter is defi

Pagina 97

72/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.4.5 Temperature control with LG-Ni 1000 se

Pagina 98

73/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.4.6 Bypassing the VSDThere are application

Pagina 99

74/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P1263Defines the time delay between the bypa

Pagina 100

75/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.4.7 Hibernation modeIf the VSD reaches the

Pagina 101

76/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2390Hibernation frequency setpoint [%]Setti

Pagina 102

77/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.20026.5 System parameter list for levels 1 to 3r

Pagina 103

78/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Instructions:1. Step 1: Set P0003=3 (expert

Pagina 104

79/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002r0035 CO: Act. motor temperatureDisplays mea

Pagina 105

8/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.2002Data sheetThe data sheet contains a brief de

Pagina 106

80/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Unit: - Min: - Def: - Max: -Bit fields:Bit00

Pagina 107 - 7 Troubleshooting

81/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002r0209 Maximum variable speed drive currentDi

Pagina 108 - ≤ VSD power (P0206)

82/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Data:Stator resistance value in [Ohms] for t

Pagina 109

83/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P0610 Motor I2t temperature reactionDefines

Pagina 110

84/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P0718 CO/BO: Hand / AutoSelects function of

Pagina 111

85/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002r0755[2] CO: Act. ADC after scaling [4000h]D

Pagina 112

86/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Unit: - Min: 0:0 Def: 21:0 Max: 4000:0Settin

Pagina 113 - 8 Technical data for the SED2

87/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Note:Possible PROFIBUS settings:1 ... 1250,

Pagina 114

88/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Bit13 Motor potentiometer MOP up 0 NO, 1 YES

Pagina 115 - 8.2 Type-specific data

89/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.200231=MOP setpoint + Fixed frequency32=Analog s

Pagina 116

9/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Introduction 01.20021.7 Environmental compatibility and disposal

Pagina 117

90/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Dependency:Accessible only if P0701 - P0706=

Pagina 118

91/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P1091 toP1094Skip frequency 1 through 4Defin

Pagina 119 - 9 Appendix

92/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Settings:0 =Flying start disabled1 =Flying s

Pagina 120 - 9.2 Applicable standards

93/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002722.5=Digital input 6 (requires P0706 set to

Pagina 121 - 9.3 List of abbreviations

94/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P1270[2] BI: Enable essential serviceUnit: -

Pagina 122

95/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Details:Displays actual compensated motor sl

Pagina 123 - HVAC Products Index 01.2002

96/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2009[2] USS normalizationMin: 0 Def: 0 Max:

Pagina 124

97/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002P2100[3] Alarm number selectionSelects up to

Pagina 125

98/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Unit: Hz Min: 0.00 Def: 50.00 Max: 650.00Det

Pagina 126

99/126Siemens Building Technologies SED2 variable speed drives CM1U5192enHVAC Products Programming 01.2002Note:The PID setpoint source is selected usi