Siemens APOGEE™ FLN (P1) Communication Kit
MN04008002E
For more information visit: www.EatonElectrical.com 6-1
February 2006
Chapter 6 — Communication Board Fault Tracking
The table below presents the faults related to the Siemens FLN (P1) option board. For more
fault code information, see also HVX9000 User Manual, Fault Tracking Section.
Table 6-1: Communication Board Faults
You can define with parameters how the AFD shall react to certain faults:
Table 6-2: AFD Response to Faults
Fault
Code Fault Possible cause Possible solutions
37 Device change Option board changed Reset
38 Device added Option board added Reset
39 Device removed Option board removed Reset
40 Device unknown Unknown option board Check the installation.
If installation is correct contact the
nearest Eaton distributor.
53 Communication
bus fault
The data connection between the
communication bus master and the
communication bus board has
failed.
Check the installation.
If installation is correct contact the
nearest Eaton distributor.
54 Slot fault Defective option board or slot Check that the board is properly
installed and seated in slot. If
installation is correct, contact the
nearest Eaton distributor.
Code Parameter Min. Max Unit Step Default Note
P1.7.22 Response to
fieldbus fault
03 12 0=No response
1=Warning
2=Fault, stop acc. to 2.4.7
3=Fault, stop by coasting
P1.7.23 Response to slot
fault
03 12 0=No response
1=Warning
2=Fault, stop acc. to 2.4.7
3=Fault, stop by coasting